26 Advanced UPSMON Configuration UPSMON User Manual
1.4.1 Remote sensor configuration
Name of parameter Description of parameter
Name
Name of the sensor connected to the SNMP adapter
Type of sensor
Type of sensor: temperature, humidity or digital I/O.
Name of UPS
Name of the UPS connected to the SNMP adapter with which the sensors have been associated.
Note: this combo box shows only the UPS for which the item “Remote Sensors” has been
selected in the UPS configuration (see paragraph Errore. L'origine riferimento non è stata
tt
)
Sensor Index
Index of the sensors (from 1 to 6) connected to the SNMP adapter.
Temperature and humidity
thresholds
Maximum and minimum temperature and humidity threshold settings on the sensor. When these
values are exceeded, the actions specified for the respective alarm in the section “Status and
actions” (see paragraph 1.7) will be carried out.
Note: humidity thresholds are active only for humidity type sensors.
Digital input parameter
Determines whether the digital I/O sensor has the input contact normally open (the alarm is
triggered when the contact is closed) or normally closed (the alarm is triggered when the contact
is opened). This section is active only for digital I/O type sensors.
Digital output parameter
Determines whether the digital I/O sensor must close the output contact when a general alarm
occurs on any of the sensors associated with the same SNMP adapter (switching for sensor
alarm), and/or when an alarm occurs on the UPS connected to the same adapter (switching for
UPS alarm). This section is active only for digital I/O type sensors.